SILHORKO-EUROWATER took part in a steam boiler water modernization project at a dairy plant belonging to a large international company.

Returning the hot condensate back to the boiler saves water and fuel. In this case, however, the condensate quality was not 100% pure, clean water, and further water treatment was required. Therefore, the main job was to upgrade the water treatment system on the steam boiler. The solution consists of:

  • Removal of particles and iron in a bag filter. The special bag filter is completely in stainless steel and can operate in pH range between 3 and 13, and water temperature up to 100°C
  • Removal of hardness in an ion exchange duplex softening unit with SE20 PLC control panel. The unit is designed for hot water up to 85°C
  • Both units are insulated in order to reduce temperature loss
  • Dosing system for pH control including measuring equipment and digital dosing pump for NaOH dosing

Reference ID: 139827
Industry: Food industry
Application: Boiler water

 

Download PDF

Technical data

  • Flow: 10 m³/h
  • Hardness: <0.5 °dH

Units in plant

  • Bag filter type EFG8 AISI 316
  • Hot water softener type SFHG 1202 insulated
  • Dosing system

 